Chiller Performance
Total power
# Chillers
Avg chiller load
COP
Plant efficiency
| Chiller | Status | Power (MW) | Cap. (%) | COP |
|---|---|---|---|---|
| Chiller 1 | ON | 1.1 | 100% | 5.6 |
| Chiller 2 | ON | 1.1 | 99.8% | 5.8 |
| Chiller 3 | OFF | --- | --- | --- |
| Chiller 4 | ON | 1.1 | 100% | 5.6 |
Plant COP
Setpoint Optimizer
ModeAlgorithm
Setpoint
11.8°C
# Chillers Advised
Running
3
Advised
4
Advisory follow rate
92%
CHW Temperatures
ECW
14.1°C
LCW
8.8°C
CHW Delta
5.2°C
Seawater Pumps
Pumps on
3/4
Total power
0.24MW
Common Pumps
Pumps on
2/4
Total power
0.18MW
Load Distribution
Advisory follow rate
92%
15–30%
75 hours
30–45%
317 hours
45–60%
1,148 hours
60–75%
1,295 hours
75–90%
994 hours
>90%
745 hours
Plant Energy Consumption
Plant total · last week382MWh
# Chillers on3/4
Avg load87%
COP5.7
Chillers45%172 MWh
AHUs35%134 MWh
Pumps20%76 MWh
Chillers — ranked by efficiency
| # | Unit | Status | COP | Cooling (kW) | Cond. approach (°C) | Run hours (h) | Condition | Notes |
|---|---|---|---|---|---|---|---|---|
| 1 | Chiller 2 | RUN | 5.8 | 4,260 | 1.1 | 39,880 | OK | Best performer of the plant. |
| 2 | Chiller 1 | RUN | 5.6 | 4,180 | 1.2 | 41,250 | OK | Operating on design curve. |
| 3 | Chiller 4 | RUN | 5.6 | 4,040 | 2.6 | 44,720 | ALERTCondenser cleaning | Fouling suspected · Hunting |
| — | Chiller 3 | STOP | — | — | — | 36,540 | OK | Stopped — standby. Last run 14 Aug (18 h): COP 4.6, 0.71 kW/RT, no flags — healthy. |
Condition & maintenance advisory
1 open item- Clean condenser tubes — Chiller 4HIGH PRIORITYDue: Within 7 days
High condenser approach (2.6 K) and 14% suction drop indicate fouling — plan a condenser tube clean to recover COP.