Intelligent HVAC control
11:42 UTC
Summary

AHU summary

Energy, performance and comfort metrics across all 119 air handling units — totals and averages per area.

Fleet totals

Energy
AHUs on
110/119
Total power
2463.3kW
Avg power/unit
20.7kW
Comfort level
Avg fan speed
90%
Avg SAT
16.1°C
Avg cooling valve
75%
Avg heating valve
22%
Avg return temp
24.7°C
Avg return humidity
60%
Avg zone temp
23.4°C
Avg CO2 SP/actual
669/622ppm

Energy and comfort by area

Totals and averages per area group · click a header to sort
AreaEnergyComfort level
AHUsTotal power (kW)▼Avg power/unit (kW)Avg fan speed (%)Avg SAT (°C)Avg cooling valve (%)Avg heating valve (%)Avg return temp (°C)Avg return humidity (%)Avg zone temp (°C)Avg CO2 SP/actual (ppm)
Passenger Cabins
32773.624.28714.6
72
18
24.55823.6600 / 580
Public Areas
21613.829.210016.5
85
28
24.06223.8650 / 610
Galleys & Dining
26390.915.08717.1
70
14
25.26523.4700 / 640
Crew Spaces
17356.120.98215.8
68
31
23.85523.2600 / 560
Technical & Other
23328.914.310017.0
82
25
25.56023.0800 / 720

Top AHU consumers

Ranked by power consumption
AHULocationPower consumption (kW)Fan speed (%)SAT (°C)CO2 SP vs actual (ppm)
504Atrium PS Dk 5-6-766.1100%19.0600 / 580
204Back Stage - Main Lounge Dk 5-6-763.099%17.0650 / 610
306Pax Stairs51.0--16.0600 / 560
501Crew Cabins Dk 2-3-444.797%15.2600 / 560
810Pax Cabins Dk 7-8-9 SB43.185%14.4650 / 620
614Crew Galley Dk 439.8--20.0800 / 720
505Atrium SB Dk 5-6-736.0--18.0600 / 580
402Fore Crew Cabins Dk 2-435.896%16.4600 / 560

Largest setpoint deviations

Supplied air temp vs setpoint
  • 710
    Pax Cabins Dk 12-13
    20.7 °C actual · 15.0 °C setpoint
    +5.7 °C
  • 712
    Cafeteria PS & SB Dk 14
    19.3 °C actual · 14.0 °C setpoint
    +5.3 °C
  • 708
    Pax Cabins Dk 8-9
    19.8 °C actual · 15.1 °C setpoint
    +4.7 °C
  • 814
    Pax Cabins Dk 11-15 PS
    17.1 °C actual · 13.0 °C setpoint
    +4.1 °C
  • 713
    Cafeteria PS & SB Dk 14
    18.0 °C actual · 14.0 °C setpoint
    +4.0 °C
  • 218
    Pax Cabins Dk 16 - Pulley Dk 18
    15.5 °C actual · 12.0 °C setpoint
    +3.5 °C

Condition & maintenance advisory

2 open items
  • Replace fan belt — AHU 014HIGH PRIORITYDue: Within 5 days

    Vibration trend up 18% and belt slip alarms — schedule belt replacement to restore fan efficiency and avoid motor overload.

  • Clean cooling coil — AHU 047MEDIUM PRIORITYDue: Within 14 days

    Cooling valve at 92% while SAT drifts 1.4 °C above setpoint — coil fouling suspected, plan a chemical clean to recover cooling capacity.