Chiller KPIs
Per-unit efficiency and operating point — click a column to sort| Chiller 1 | RUN | 4,180 | 1,100 | 5.6 | 100.0 | 100 | 6.2 | 27.8 | 0.9 | 1.2 | 88 | 3.5 | 8.4 | 41,250 |
| Chiller 2 | RUN | 4,260 | 1,100 | 5.8 | 99.8 | 100 | 6.3 | 27.7 | 0.8 | 1.1 | 86 | 3.6 | 8.3 | 39,880 |
| Chiller 3 | STOP | — | — | — | — | — | — | — | — | — | — | — | — | 36,540 |
| Chiller 4 | RUN | 4,040 | 1,100 | 5.6 | 100.0 | 95 | 5.3 | 29.2 | 1.8 | 2.6 | 58 | 3.4 | 8.9 | 44,720 |
Trends
One chart per chiller · toggle the metrics to plotChiller 1RUN
Chiller 2RUN
Chiller 3STOP
Stopped — no trend data
Chiller 4RUN
Subsystem detail
Compressor · motor · condenser · evaporator — all unitsCompressor
| CH1 | CH2 | CH3 | CH4 | |
|---|---|---|---|---|
| Suction pressure kPa | 352 | 358 | — | 341 |
| Suction sat. temp °C | 5.9 | 6.1 | — | 5.4 |
| Discharge pressure kPa | 842 | 831 | — | 894 |
| Discharge gas temp °C | 58.4 | 57.1 | — | 64.8 |
| Discharge superheat K | 6.2 | 5.8 | — | 9.4 |
| Suction drop % | 6 | 5 | — | 14 |
Motor
| CH1 | CH2 | CH3 | CH4 | |
|---|---|---|---|---|
| Motor current A | 1412 | 1398 | — | 1455 |
| Winding temp °C | 74 | 72 | — | 86 |
| DE bearing temp °C | 58 | 57 | — | 66 |
| NDE bearing temp °C | 55 | 54 | — | 62 |
| DE vibration mm/s | 1.8 | 1.6 | — | 3.4 |
| Oil pressure kPa | 214 | 219 | — | 198 |
Condenser
| CH1 | CH2 | CH3 | CH4 | |
|---|---|---|---|---|
| Sat. cond. temp °C | 26.1 | 25.6 | — | 28.9 |
| Entering seawater °C | 21.6 | 21.6 | — | 21.6 |
| Leaving seawater °C | 24.9 | 24.5 | — | 26.3 |
| Seawater ΔP kPa | 58 | 56 | — | 71 |
| SW valve feedback % | 82 | 79 | — | 100 |
| Liquid level % | 48 | 51 | — | 39 |
Evaporator
| CH1 | CH2 | CH3 | CH4 | |
|---|---|---|---|---|
| Sat. evap. temp °C | 5.2 | 5.4 | — | 4.1 |
| Entering CHW °C | 12.4 | 12.3 | — | 12.6 |
| Leaving CHW °C | 7.1 | 7 | — | 7.3 |
| CHW ΔP kPa | 64 | 62 | — | 69 |
| CHW ΔT K | 5.3 | 5.3 | — | 5.3 |
Chiller event log
Last 24 hours- 14:20Chiller 4Efficiency flag raised — kW/RT 0.78 vs 0.74 plant average
- 12:05Chiller 4Hunting detected on capacity valve (12% of bucket)
- 09:40Chiller 2Demand limit released to 100%
- 06:15Chiller 3Stopped — sequenced out on low plant load
- 02:30Chiller 1Started — sequenced in on rising load